Search SR SysTech Solutions

Try “Fire Alarm”, a brand name, or a model number.

Menu
ADDRESSABLE ZONE INTERFACE MODULE
RAVEL

RAVEL

ADDRESSABLE ZONE INTERFACE MODULE

Fire Alarm System ADDRESSABLE ZONE INTERFACE MODULE RE-717MZ

Zone Interface module permits the addressable FACP to interface and monitor 2-wire / 4-wire conventional smoke detectors and manual call point.

Key Features

  • Complies UL standard.
  • CE Approved.
  • Module Status by RED LED.
  • Analogue Communication with the panel.
  • Module Addressing by 8 way DIP Switches.
  • Low Standby Current.
  • 24V Monitoring resettable output.
  • Available with suitable back boxes.

Specifications

Operating Voltage
24 VDC Nominal
Current Draw(SLC)
500µA, (2 mA Max.Latched)
External Supply Voltage
Regulated 24VDC
ExternalSupply Standby Current
5mA
ExternalSupply Alarm Current
60mA Max
Loop Impedance
40 Ohms
End Of Line Resistor
4.7K Ohms
Temperature Range
0 o C to 49o C / 32o to 120o F
Storage Temperature
0 o C to 60o C
Humidity
93 ± 2% RH (non-condensing) at 32 ± 2° C / 90 ± 3° F

Product Description

Zone Interface module permits the addressable FACP to interface and
monitor 2-wire / 4-wire conventional smoke detectors and manual call point.
The Zone module is addressed by using the DIP switch to communicate with
addressable FACP. It transmits the status (normal, open, short or alarm) of
one zone of 2-wire / 4- wire detectors to the FACP. Zone module supervises
the zone of detectors and the connection of the external power supply
respectively.