Search SR SysTech Solutions

Try “Fire Alarm”, a brand name, or a model number.

Menu
Beam Detector
RAVEL

RAVEL

Beam Detector

Fire Alarm System Beam Detectoe RE-428 Series

Optical Beam Detector 100mtr.

Get Latest Price

Key Features

  • User Friendly Installation.
  • In built laser light for easy alignment.
  • Supports 5 to100 meter range.
  • Option for Remote Indication.
  • Provision to connect with Fire Man Telephone System.
  • Adjusting Screws at detector for precise alignment.
  • Infrared transmitter & receiver located in a single housing.
  • In built drift compensation for monitoring dirt build up on the optical system.
  • Sensitivity Threshold :- 18% ,30%, 50%

Specifications

Operating voltage
24V
Quiescent current
20 mA
Alarm current
60 mA
Current at radiation beam interruption
< 0.3 mA
Operating distance range for RE-428FR reflector
5 to 50 m
Operating distance range for RE-428HR reflector
50 to 100 m
Sensitivity thresholds (optional)
18%, 30%, 50%
Power supply of laser target viewfinder (during alignment)
9 V (6F22) battery
Operating temperature range
-25 C to 55 C
Relative humidity
up to 95% at 40 C
Dimensions
128 x 79 x 84 mm
Mass
0.35 kg

Product Description

TheRE-428 Series beam smoke detector is designed for smoke detection at the start of a fire. It is especially
suitable for protection of indoor spaces, in which the appearance of smoke is likely during ignition of a fire, and
where, due to a large space area, installation of a greater number of point smoke detectors would benecessary.
The RE-428 Series beam smoke detector and the prism reflector or reflector panel are installed on opposite
walls of a room.