Fire Alarm System Multi Sensor Detector RE-317D-SHL

Addressable Multi Sensor Detector.

Get Latest Price

Key Features

  • UL listed and NFPA standard.
  • Polarity free, Dual LED’s, and 360°visibility.
  • Insect Filter.
  • Fixed temperaure and rate of rise detection.
  • Advanced detection and communication protocol.
  • Easy to install.
  • Sleek low-profile housing design.
  • Regular 100mmbase.
  • Address set by 8 digit DIP switch.

Specifications

Operating Voltage
17 ~ 28V DC.
Reset Voltage
Less than 3V.
Standby Current
500 µA.
Start up Time
30sec.
Alarm Current
5 mA .
Remote Output
2mA maximum open collector.
Thermal Rating
59° C (138° F).
Rate of Rise of Temperature
11.1° C / min (20° F/min).
Smoke Sensitivity
(2.12 ± 0.61) % obs/ ft. (High: 1.1; Medium: 1.4; Low: 2.3) % obs/ft
Air Velocity
0 – 4000 fpm
Detector Spacing
9 meters
Operating Temperature
-10° C to 37.8° C
Storage Temperature
-10° C to 60° C.
Humidity
0 – 95% RH, non-condensing.
Dimension
60 H with base x 100 D (mm)
Weight
150 g with base
Material
FR ABS plastic
IP Rating
IP-42

Product Description

Addressable multi sensor detector(s) are designed to work with Addressable panel.
These detectors are low profile, polarity free and have dual LED’s for 360° visual
indication. The LED’s are blinking in normal operating condition whereas the LED's
in steady state indicate fire status. The fixed cum rate of rise heat detector works
using a thermistor. These detectors will raise an alarm when the detector reaches
59°C (Fixed) or when the change in temperature exceeds the rate of rise @ 11°C /
min.It has an unique chamber designed to sense smoke produced bywide range of
sources of combustion with insect free. The detectors sensitivity can be
programmed via FACP. It has a unique drift compensation feature wherein the
detector adjusts its normal referencebasedonenvironment conditions.